3. [Get Info] From 2-Way Driver
2-way KNX driver for COMM-TEC CTG-KNX/IP and CTG-EIB/NX
This driver is used to control and monitor KNX installations with the COMM-TEC CTG-KNX/IP (IP) or
CTG-EIB/NX (RS232) Gateway. The KNX installation is controlled by setting values for KNX configured
groups or getting values from these groups. This driver does not use polling, the needed KNX values must
be configured in ETS to be automatically sent by the KNX modules. The COMM-TEC gateway reads
these values from the KNX bus, as they appear. To configure the driver you need to know the existing
KNX groups and their functions / value types. Every KNX group you wish to control/monitor, must be
configured in your driver. On startup of the XP-8, the COMM-TEC gateway is initialized and configured
with the KNX physical address, the groups and data types you entered in the driver configuration.
You can use up to 250 KNX groups and up to 10 Events with one driver/COMM-TEC gateway!
Driver configuration parameters:
Connection
Communication Interface
CTG-KNX/IP gateway via IP or CTG-EIB/NX gateway via RS232
IP address (CTG-KNX/IP)
IP address of the COMM-TEC gateway (e.g. 192.168.1.1).
IP Port (CTG-KNX/IP)
IP port of the COMM-TEC gateway ( default: 10002 ).
Serial port (CTG-EIB/NX)
RS232 port of the XP controller
KNX physical address of gateway
Unique KNX address of the COMM-TEC gateway (e.g. 1.1.254), must match KNX area
and line segment numbers.